Two and a half years of leaks, and the roof was never the problem
Case study: Forensic water intrusion investigation
An owner had paid for repair after repair on the roof above two storefront windows. The leaks kept coming back. We were asked to find the real source.
At a glance
- Building: Single-story industrial and office building, built in the late 1990s
- Location: Lake Norman area, North Carolina
- Services: Forensic water intrusion investigation, infrared thermography, moisture mapping, water testing
- Standard: ASTM E2128 (evaluating water leakage of building walls)
- Result: Source confirmed at the storefront-to-wall joint, with a repair plan the owner could bid
The problem
Staff had reported water at a storefront window in a front office for about two and a half years. Several repair attempts had been made at the windows and at the metal roof directly above them, and none of them held. Once we started asking questions on site, a second storefront in a nearby conference room turned out to have the same history.
What we did
We started inside. An infrared camera showed cool, irregular patterns around both window openings, and a pin-type moisture meter confirmed wet drywall at the sills, the jambs and just above the heads. Outside, we documented poor sealant at the window perimeters, gaps in the cladding where the upper EIFS met the split-face block below, and some hairline cracking in the block.
Then we tested. Using a calibrated spray nozzle, we wet one small zone of the window at a time for a set period and watched the moisture readings inside. The bottom corners stayed dry. When we moved to the middle of the jamb, the interior readings rose within minutes, and the head-to-jamb corner did the same. Two small inspection cuts showed water getting past the cladding and running around the window frame into the wall opening. Nothing pointed to the roof.
What we found
The water was entering between the storefront frame and the wall opening, where the window was never properly tied into the wall's waterproofing. This is one of the most common storefront failures we see, because those integration points are easy to miss when trades are sequenced quickly. The break between the EIFS and the block added a second path if the weather barrier behind the cladding was not continuous.
What we recommended
Remove and reinstall both storefronts with proper integration to the weather barrier, which means opening up the cladding around each opening. If full removal was not practical, partial cladding removal was still needed to correct the integration at the jambs and heads. We also recommended sealing the cladding transition and checking similar conditions elsewhere on the building.
Why it matters
Testing one small area at a time is what separates a guess from a diagnosis. Here it saved the owner from paying for another roof repair and pointed the contractor straight at the joint that was actually failing.
Client and property names are kept confidential. References are available on request.